A PHP Error was encountered

Severity: Notice

Message: Undefined index: name

Filename: controllers/products.php

Line Number: 90

Cablofil Ladder Tray:

Wall Penetration Sleeve

Wall Penetration Sleeve Catalog Numbering Example:
6 M 2 - 0440 - 36 - CD
Side Rail Height Material
M
G
L
T
Fitting Series
This item must be specified as Series 2
Product No. Width
06 - 6"
09 - 9"
12 - 12"
18 - 18"
24 - 24"
30 - 30"
36 - 36"
Fastener Options
CD
S6

M

Mill Galvanized Steel

G

Steel,
Hot-dip galvanized

L

Type 304 Stainless Steel

T

Type 316 Stainless Steel

Fabricated cable tray fire stop sleeves from Legrand®/Cablofil, combined with Hilti Firestop products, are an economical alternative to the high cost of fabricating protective fire wall and floor penetration sleeves in the field.

This firestop system provides a rigid support for cable tray in a UL classified system approved for fire wall and floor penetrations. After the sleeve is placed in the wall or floor, the loose collar slides over it. Hardware for the tray connection only is included. Hardware required to mount sleeves to the wall or floor is not included.

The Hilti Fire Block is a compressible fire stop brick, well-suited for installations where frequent cable changes may be required. Blocks are easily cut to fit any space, and can be removed and reinstalled when cable configurations change. When exposed to fire, the blocks expand to lock the seal in place.

PRODUCT NUMBER
0440
FASTENER OPTIONS
CD Cadmium-plated Steel
S6 316 Stainless Steel

Each cable tray firestop sleeve includes:

- One penetration sleeve with flanges

- Hilti Fire Blocks

- One Hilti Firestop Putty Stick

- Hardware for cable tray connection to the wall sleeve:

  • Metallic and fiberglass cable trays with two side rails: the Firestop kit includes two pairs of splice plates with nuts & bolts. 316 stainless steel is recommended for use with fiberglass systems.
  • Cable runway systems: two J-bolts with hardware are included for connecting the cable runway to the sleeve. Sleeves are 4" deep for all runway systems.
NUMBER OF HILTI FIRE BLOCKS
INCLUDED WITH EACH SLEEVE
SLEEVE WIDTH SIDE RAIL HEIGHT (IN.)
4 5 6 7
6 2 2 3 3
9 3 3 4 4
12 3 4 5 6
18 5 6 7 8
24 6 8 9 11
30 8 10 12 14
36 9 12 14 16

UL classified for use with:
2-hr concrete or block walls
2-hr concrete floors
1-hr gypsum walls
2-hr gypsum walls

WALL/FLOOR SLEEVE DESCRIPTION
Designed for single runs of cable tray, having a height and width to match the tray system specified. One end of the 20 inch sleeve has a flange attached 6 inches from the end, while the flange for the other end is "floating" and is free to slide directly against the face of the wall as needed. The 20 inch length of the sleeve will accommodate a wall thickness of up to 8 inches. A wall thickness of 8 inches will result in the sleeve protruding 6 inches from each side of the wall. Both ends of the sleeve are punched with holes for attaching cable tray splice plates or hardware needed for the tray system specified.

INSTALLATION
The opening in the wall should be within 1 inch of the nominal height and width of the cable tray. The flanges of the sleeve have 7/16" diameter mounting holes for attachment to the wall using 3/8" diameter hardware. Hardware for wall attachment is not included. After the sleeve is mounted in the wall or floor, the cable trays on either side of the sleeve can be connected using the hardware supplied with the sleeve. When the trays are in place, the cables should be pulled through the wall and sleeve as needed. After all of the cables are installed in the tray, install the Fire Blocks as described. Any voids between cables should be filled with the Firestop Putty Stick.

TECHNICAL DATA

Construction Arc Welded
Sleeve Dimensions 20" x Tray Width x Tray Height
Flange Dimensions (Tray Width + 6") x (Tray Height + 6")
UL Classification Qualifies for use as an equipment grounding conductor per N.E.C. 392.7. Cross-sectional area and amperage ratings are based on the cable tray system attached to the sleeve.

HILTI FIRE BLOCKS INSTALLATION:
Walls: Hilti Fire Blocks shall be installed with 5" dimension projecting through and centered within wall assembly. Floors: Hilti Fire Blocks shall be installed with 5" dimension projecting through opening, flush with the top surface of sleeve or recessed within sleeve at any level above the top surface of floor. Fire blocks fill the annular space between the cables and the sleeve. Fire Blocks may be cut to match the profile of cables or to fit opening. Any voids should be filled with 0618 Firestop Putty Stick.